(857) 837-1475Get an Estimate

Service

Whole-home heat pump installation in Boston, MA

One ducted system that heats and cools the whole house, with the furnace or boiler retired.

Last Updated:

Ducted cold-climate heat pump outdoor unit on a raised stand behind a two-story Boston colonial in winter, with snow on the lawn
SizedFrom a room-by-room load calculation at your town's design temperature
MeasuredDuct static pressure and airflow before and after
TestedNitrogen pressure test and deep vacuum before the charge
In writingEquipment, duct work, electrical and permits listed line by line

Inside a Roslindale whole-home heat pump job

Before: the original attic air handler on flex ducts, Roslindale, near Roslindale Village
Before: the original attic air handler on flex ducts
New attic air handler on a platform with a secondary pan, Roslindale, near Roslindale Village
New attic air handler on a platform with a secondary pan
Two outdoor units on an 18-inch stand, Roslindale, near Roslindale Village
Two outdoor units on an 18-inch stand

The house and the problem

A 1920s colonial with a 22-year-old gas furnace in the basement and a 4-ton AC in the attic. The basement ducts only reach the first floor; the attic unit only cools the second. Upstairs is hot in July, and the back bedrooms are cold in January.

What the measurements decided

The load calculation comes to 36,400 BTU an hour on a 7°F night, split roughly 58/42 between the floors. One big unit pushed through the basement ducts never reaches upstairs, so we put two right-sized systems on the ducts each floor already has: 2 tons in the basement, 1.5 tons in the attic.

The work

Furnace, attic air handler and condenser out, refrigerant recovered. A variable-speed air handler with 5 kW of backup heat on the basement plenum, plus a second return in the upstairs hall, because static pressure reads 0.82 inch before the change. In the attic, the leaking flex replaced with sealed, R-8 insulated duct, and the new air handler set on a platform with a secondary pan and float switch. Both outdoor units on an 18-inch stand 11 feet from the rear lot line, inside Boston's nighttime noise limit.

Before we call it done

Line sets are brazed under nitrogen, pressure-tested, pulled below 500 microns and charged by weight for the 25- and 42-foot runs. Airflow and static are measured again, a licensed gas fitter caps the gas line, and the aux heat locks out above 15°F. Because the furnace comes out, the job qualifies for Mass Save's whole-home path.

Project facts
ServiceWhole-home heat pump, two systems
WhereRoslindale, near Roslindale Village
House1920s colonial, about 1,850 sq ft
BeforeGas furnace and a 4-ton attic AC
After2-ton basement and 1.5-ton attic heat pumps
Price$27,400 before rebates
Time on siteFour working days

Upstairs is an oven in July, the back bedrooms are cold in January, and the furnace and the AC are both past 20. Clement Boston Heat Pumps installs whole-home ducted heat pumps across Boston and the towns within 20 miles: one system that heats and cools the house, with the furnace or boiler retired.

We size it from your house, not from the old unit, and put the plan in writing before anyone talks brands. Our typical range for a whole-home system on ducts we can reuse is $15,000 to $28,000 and up, before rebates.

What “whole-home” means

A whole-home heat pump carries all of the heating, every night of the year, with nothing burning fuel beside it. In summer the same system cools.

How it works

The outdoor unit pulls heat from outside air even below zero. A copper line set carries it inside, and an air handler pushes it through your ducts. A reversing valve flips the flow for cooling.

How it differs from the alternatives

A dual-fuel system keeps your furnace for the coldest hours. A partial system heats one floor while the boiler heats the rest. Whole-home is the choice when you want one system type, one kind of fuel bill and the old equipment gone.

It’s also the path Mass Save rewards most: a per-ton rebate that requires the old system removed or disconnected. Our Mass Save rebate guide compares the paths.

What happens on the first visit

We measure the house, test the ducts, check the panel and find a spot for the outdoor unit. All four go into the written estimate.

  • The load calculation. A room-by-room calculation using the ACCA Manual J method: walls, windows, insulation, air leaks and your town’s design temperature. Boston sizes to 7°F at Logan; inland towns such as Waltham and Woburn run colder.
  • The ducts. Static pressure across the furnace or air handler, the size of the return, and leaks at the trunk joints and in any attic runs. Heat pumps move more air than furnaces.
  • The panel. Whether the service has room for the heat pump and its backup heat, or needs an upgrade.
  • The outdoor spot. A stand above drifting snow, out from under the drip line, and far enough from the lot line to meet your town’s noise rules.

You get it back in writing: the equipment and its capacity at 5°F, every duct change and why, the electrical work, the permits, the rebate path and our price.

Why same-size replacement is the wrong start

Copying the tonnage off the old AC is the most common mistake in a conversion. Older systems were often sized by rule of thumb, and many furnaces are far larger than the house needs.

Oversized

An oversized heat pump reaches the setpoint fast, shuts off, and leaves summer air clammy because it never runs long enough to pull out moisture.

Undersized

An undersized one runs flat out on the coldest nights and leans on electric backup strips, which cost two to three times as much per unit of heat. That’s the January bill people complain about.

The load calculation lands between the two, and it often lands smaller than the old furnace. Mass Save pays a sizing bonus for systems sized to the home’s total heating need. Our sizing guide shows how the numbers work.

Cold weather, backup heat and the controls

Every whole-home system we install is on the ENERGY STAR cold-climate list, tested to 5°F, which Mass Save also requires. These units are variable speed.

They run slow and steady most of the winter and ramp up on the coldest nights, which keeps supply air warm and the house even. Our guide on cold-weather performance goes deeper.

The backup heat lockout

Most all-electric air handlers carry heat strips for the coldest hours and for defrost. We set a lockout so they stay off above a chosen outdoor temperature, and record it in your closeout papers. Aux heat on a mild day means a setup problem; see heat pump aux heat.

Insulation and air sealing come first

The cheapest ton of heat pump is the one you don’t need. Air sealing and attic insulation can drop a house a size before we pick equipment.

Leaks around the attic hatch, the top plates of balloon-framed walls and the basement rim joist let warm air out all winter, and every bit adds to the load. Older Boston houses have plenty.

What Mass Save asks for

Mass Save ties its whole-home rebate to weatherization: a home energy assessment with its recommended air sealing and insulation done, or a house new enough not to need it. If yours hasn’t had one, we say so before sizing, because the load drops once the work is done.

Rebates and town rules

Mass Save pays its whole-home rebate per ton for qualifying equipment installed by a participating contractor in its Heat Pump Installer Network. The per-ton rate drops on January 1, 2027.

Where the house is What applies
Eversource or National Grid electric Mass Save’s whole-home, partial-home or basic rebate, plus the winter heat pump rate
A light plant town such as Belmont, Reading, Peabody or Braintree The town utility’s own heat pump program for oil, propane and electric-heat switches
Cambridge, Arlington, Brookline, Newton or Lexington, in a major renovation No new fossil-fuel equipment, so whole-home is the route

We confirm the current figures for your address when we write the estimate. The cost guide lists the rebate amounts and our ranges side by side.

When whole-home isn’t the right call

Some houses lose so much heat that a system big enough for the coldest night is oversized the rest of the winter. Some have a five-year-old furnace. Some have ducts that can’t carry heat pump airflow without work.

In those cases we price the alternatives beside it: dual fuel with the furnace as backup, duct work first, or a heat pump for part of the house. You decide with both numbers in front of you.

What's included

Three ways to heat and cool a Boston house with ducts

Whole-home heat pumpHeat pump with furnace backup (dual fuel)New furnace and AC
What heats on the coldest nightThe heat pump, with electric backup stripsThe furnace, below the switchover temperatureThe furnace
Fuel billsElectric onlyElectric most of the winter, gas or oil in deep coldGas or oil all winter, electric for AC
Mass Save pathWhole-home rebate, per tonPartial-home rebate, per tonNo heat pump rebate
Old equipmentFurnace or boiler removed or disconnectedFurnace stays and runs lessReplaced
Fits town fossil-fuel-free rulesYesNot in a major renovation in Cambridge, Arlington, Brookline, Newton or LexingtonNot in a major renovation in those towns

Related resources

How a job runs

First call

You tell us what heats and cools the house now, which rooms aren't working, and roughly where the house is.

Home visit

We measure the house for a load calculation, test the ducts, check the panel and look for an outdoor spot.

Written estimate

Equipment, duct changes, electrical, permits and the rebate path, line by line, with our price.

Install

Permits first, then the work: usually two to five working days on site.

Commissioning

Pressure test, vacuum, charge by weight, airflow and controls set before we call it done.

Ready to retire the furnace?

Tell us what heats the house now and which rooms aren't working. We'll measure and send a written plan with our price.

Whole-home heat pumps: questions

How do I know one heat pump can carry my whole house in January?

From the load calculation. We work out how much heat the house loses on Boston's design night, 7°F at Logan and colder inland, and pick equipment whose rated output at 5°F covers it. If it can't without oversizing, we tell you and show the dual-fuel option beside it.

Do I need two systems for a two-story house?

Only when the floors already have separate duct systems or one duct system can't reach both. Many Boston colonials have basement ducts for the first floor and an attic AC for the second; those usually get two smaller systems instead of one oversized one.

What happens to my old furnace or boiler?

For a whole-home system it comes out or is disconnected, with the gas line capped by a licensed gas fitter or the oil line capped. That's what Mass Save's whole-home rebate requires, and it's what makes the system whole-home rather than a backup arrangement.

Does Mass Save's whole-home rebate have other conditions?

Yes. The equipment has to be on the cold-climate list, the installer has to be in the Heat Pump Installer Network, and the house needs proof of weatherization, such as a recent home energy assessment with its recommendations done. We check where your house stands before the estimate.

How long does a whole-home install take?

Most take two to five working days on site once the permits are in hand. Two systems, an attic air handler, a service upgrade or duct rebuilding push toward the longer end. The heat is off for part of the job, so in winter we plan around a temporary source.

Related services

Get an estimate for whole-home heat pumps

Tell us what heats it now and which rooms aren't working. We'll measure, lay out the system and the ducts, and put the plan and the price in writing.

Step 1 of 2

The house and the work